The permitted length of the bus cable within a line segment is between 1 000 m and 2 000 m, depending on the data-transmission rate.
False
False. The length rules of a TP line segment do not depend on the transmission rate, because KNX TP operates at a fixed 9 600 bit/s. The applicable rules are constants: 1 000 m total cable length per line segment, 350 m between any device and its power supply, and 700 m between any two devices. There is no 2 000 m option that you can unlock by changing a bit-rate parameter.
Memorise the 1 000 / 700 / 350 m triplet — it comes up in nearly every exam batch and in nearly every real survey when sizing a complex line.
Keep going with the full KNX Basic bank
Keep going with the full KNX Basic bank: unlimited timed mock exams, detailed answers, history. From €9 (one-time payment).
See pricing — from €9 →See the 9 other KNX Basic practice questions
Related questions
- A KNX TP installation can accommodate at most 14 400 devices without using repeaters.2. TP Topology · Maximale Geräteanzahl ohne Repeater
- A KNX TP1 line may be divided into a maximum of 4 physical segments, each of 64 devices, giving 256 devices per logical line.2. TP Topology · Segmente pro logischer Linie
- On a KNX device, the configuration parametrised by ETS is stored in non-volatile memory (EEPROM or Flash), whereas the runtime states (current values of the Group Objects) live in volatile RAM.3. Bus Devices · Speicher einer BCU
- An RF Coupler (Media Coupler) acts as a gateway between a KNX RF segment and a KNX TP segment, allowing RF devices to take part in the same logical installation as TP devices.4. KNX RF · RF Coupler
- The Individual Address of a KNX device is used to switch electrical loads on and off.1. System Overview · Offizielle Musterprüfung 3