Free tool · KNX

KNX TP topology validator

Choose a model: classic TP-64 (64 devices per segment, up to 4 segments per line with repeaters) or one all-TP-256 segment (up to 256 devices). Both models allow 15 secondary lines per area and 15 areas.

Free · no sign-upLast updated: 2026-10-14

Segment capacity depends on the model: 64 interfaces for TP-64, 256 for fully compatible TP-256. Coupler and repeater interfaces count too. An acceptable total can hide an overloaded segment; verify the actual distribution.

Mixed TP-64/TP-256 installations depend on product electrical loads and are not calculated here.

1 to 15 areas (AA = 1–15)
1 to 15 secondary lines (LL = 1–15)
1–256 interfaces per line; 64 per segment, including couplers and repeaters
1 to 4 for the selected model

Explore the topology

Select a level. This diagram shows logical hierarchy, not a wiring plan.

0.0.x connects areas through area couplers A.0.0. Area number 0 is reserved for the backbone.

60 bus interfaces per line, including couplers and repeaters.

A.L.x — Segment 1
Power supply with choke ↓
A.L.0 → Bus interfaces per secondary line

Three worked examples

  1. 1. A simple line

    1 area × 1 line × 40 participants = 40. One segment is enough in this model, subject to current and distance checks.

  2. 2. An extended line

    1 area × 2 lines × 100 participants = 200. Two segments per line are needed: account for repeaters and their power supplies.

  3. 3. Multiple areas

    2 areas × 3 lines × 180 participants = 1,080. Three segments per line meet this simplified calculation. Main/backbone line participants are excluded from this total.

Find the error

A TP1-64 line has 90 participants on one segment. A learner suggests adding a power supply to exceed the limit. Is that enough?

How to use

1. Choose the model and enter positive integers for areas, secondary lines, bus interfaces and segments. 2. In classic TP-64, every extra segment needs its own repeater and a suitable choked supply. TP-256 mode covers one fully compatible segment. 3. Count coupler and repeater interfaces in each segment; check their distribution and consumption. 4. Cable lengths: 1,000 m per segment, at most 350 m from supply to device and 700 m between devices. Supply characteristics and total consumption must be checked separately.

Sources and scope

References: KNX Basic documentation, Topology chapter, and KNX TP1 System Specifications. Check the edition, TP1 device type and manufacturer datasheets. Cable distances and current capacity require separate checks.

KNX Association — new TP1-256 topologySiemens — distances and cable lengths (CE1P3127en, central supply, KNX-specified cable)

KNX Basic score calculator →

Practice now

Put your KNX Basic knowledge into practice

10 explained practice questions, no sign-up. Find your first topics to revisit.

Go deeper

Partial educational check of the described models, not a compliance certificate. References: KNX TP1-256 (KNX Association, 2019) and KNX Installation course. Independent CertifBus tool.

Last updated: 2026-10-14

Put this knowledge into practice
Catalogue
KNX BASIC

Your next study session starts with 10 questions.

Try the questions and explanations without an account. Then choose an access period that fits your preparation.

+1 / −0.5 / 0 official scoringFR·EN·DE interface and explanations€9 from · one-time payment
Newsletter

Keep your KNX preparation moving

We’ll email you when new KNX questions, a guide or a tool is published. No spam.

Unsubscribe in 1 click. No sharing with third parties.