During a PROFIBUS to PROFINET migration, existing GSD files must be replaced by their GSDML equivalents (the PROFINET XML format); some migration tools can generate an approximate GSDML from a GSD, but new device certifications require a native vendor GSDML.
True
GSD (PROFIBUS, ASCII) and GSDML (PROFINET, XML) are not interchangeable, and there is no reliable 1:1 automatic conversion because the underlying structures differ. If the device itself is migrated (PROFIBUS DP to PROFINET via a firmware upgrade), the vendor supplies a fresh GSDML. If the legacy device is kept behind an IE/PB Link proxy, only the GSDML of the proxy is needed (the underlying PROFIBUS slaves are invisible on the PROFINET side). The migration plan must always validate the GSDML files supplied by the vendor before cutover.
Reject any "auto-converted" GSDML during migration: insist on the vendor's official GSDML, otherwise diagnostic and parameter mapping will eventually drift from reality.
PROFIBUS bank in preparation
The full PROFIBUS bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →See the 9 other PROFIBUS practice questions
Related questions
- Which DP version introduces acyclic services for asynchronous configuration and diagnostics?1. Architecture · DP-V0 / V1 / V2
- PROFIBUS PA is the DP-V1 extension dedicated to process instrumentation, using the MBP (Manchester Bus Powered) physical layer specified in IEC 61158-2 at 31.25 kbps, which carries both power and data on the same twisted pair and is intrinsically safe for hazardous areas.1. Architecture · PROFIBUS PA
- What is the maximum segment length allowed for PROFIBUS DP at the top bit rate of 12 Mbps?2. Physical layer · Baudraten und Distanzen
- PROFIBUS RS-485 active terminations (a 390 / 220 / 390 ohm resistor network biased from 5 V) must be present at both ends of the segment and powered; the bus will not work reliably if the terminations are passive or unpowered.2. Physical layer · Aktive Abschlüsse
- What is the maximum segment length for a PROFIBUS DP Type A cable at 1.5 Mbps?2. Physical layer · Distanzen bei 1,5 Mbit/s