What is the maximum segment length for a PROFIBUS DP Type A cable at 1.5 Mbps?
C — 400 m
At 1.5 Mbps a Type A segment is limited to 400 m, which is the correct answer. 1 200 m is wrong: that is the limit for bit rates up to 187.5 kbps. 1 000 m is wrong: that is the limit at 500 kbps. 200 m is wrong: there is no PROFIBUS standard step at that value, the next bands below 400 m drop directly to 100 m for 3 to 12 Mbps. 1.5 Mbps is a popular real-world choice because it offers a workable compromise between speed and segment length.
Drill the distance/bit-rate ladder until you can recite it cold: 1200 m up to 187.5 k, 1000 m at 500 k, 400 m at 1.5 M, 100 m from 3 M onwards.
- A.1 200 m
- B.1 000 m
- C.400 m✓
- D.200 m
PROFIBUS bank in preparation
The full PROFIBUS bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →See the 9 other PROFIBUS practice questions
Related questions
- A PROFIBUS RS-485 segment supports up to 32 nodes ("unit loads") without a repeater; beyond that, RS-485 repeaters must be added, and each repeater itself counts as a unit load.2. Physical layer · Unit Loads
- A PROFIBUS GSD file (Generic Station Description) is a standardised ASCII file supplied by the device vendor; it contains the device characteristics (vendor, ident_number, supported baud rates, modules, parameters) needed to integrate it in the PLC project.4. GSD files · ASCII-Format
- A compact PROFIBUS DP slave has an I/O configuration that is frozen at manufacturing time (e.g. a 32-bit encoder, a 4-module pressure transmitter), which simplifies configuration but limits flexibility.4. GSD files · Kompaktslave
- PROFIBUS DP slave addresses range from 0 to 125 (usable); address 126 is reserved as the factory commissioning address and 127 is the broadcast address (no data exchange).5. Addressing · Adressbereich
- ProfiTrace from Procentec is the reference diagnostic tool for PROFIBUS: it captures telegrams in real time, provides statistical analysis (error rates, cycle times) and embeds an oscilloscope for RS-485 physical signal quality.6. Diagnostics · ProfiTrace-Tool