The programming button on a KNX product or the BCU has to be pressed to allocate the Group Addresses during the commissioning stage.
False
False. The programming button puts the device into 'programming mode' so that ETS can write its Individual Address (Physical Address), not its Group Addresses. Once the Individual Address has been downloaded, the application program and the Group Address links are downloaded over the bus using that Individual Address as the destination, with no further button press required. Confusing the two downloads is one of the most common Basic-exam pitfalls.
Rule of thumb: press the programming button only for the Individual Address download; application and Group Addresses afterwards travel silently over the bus.
Keep going with the full KNX Basic bank
Keep going with the full KNX Basic bank: unlimited timed mock exams, detailed answers, history. From €19 (one-time payment).
See pricing — from €19 →See the 9 other KNX Basic practice questions
Related questions
- On how many bits is the Group Address encoded inside a KNX TP1 telegram?2. TP Topology · Kodierung der Gruppenadresse
- The Group Address space in KNX TP1 allows up to 65 536 different Group Addresses (2^16).2. TP Topology · Adressraum Gruppenadressen
- Within a KNX area, the maximum number of Line Couplers is 15, one per subsidiary line.2. TP Topology · Bereichsbegrenzungen
- The 'Reset Device' command in ETS performs a software restart of a KNX device without erasing its individual address or its application configuration.7. ETS Programming · Geräte-Reset
- A single Group Object can be associated simultaneously with several Group Addresses in ETS, which is typically used so that an actuator reacts to several commands (e.g. individual command + zone command + scene).7. ETS Programming · Multi-Binding