Question
DALI bus power supplies are typically available at 100, 120, 150 or 250 mA depending on the vendor (ABB BCO/S, Tridonic DALI-PS, Lunatone PS5), and should be sized for the cumulative current of control gear plus input devices, with a 30 percent margin.
DALI-2LearnBest practicesMedium
Answer
True
Standard DALI PSU ratings give roughly the following gear budgets: 100 mA for about 15 gear, 150 mA for about 25 gear, and 250 mA for about 40 gear plus input devices. A 30 percent margin is recommended for inrush peaks and future extension. The PSU is often integrated into the KNX/DALI gateway itself to save components. Always verify the exact draw of every gear (some still draw 10 mA).
Waitlist
DALI-2 bank in preparation
The full DALI-2 bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →Want more?
See the 9 other DALI-2 practice questions
Related questions
- DALI-2 (IEC 62386 Edition 2, 2014+) is the major evolution of DALI v1, adding native support for input devices (sensors, push-buttons) directly on the DALI bus itself, together with a product certification programme administered by the DALI Alliance (DiiA).1. Architecture · DALI vs DALI-2
- The DALI bus uses a polarity-free twisted pair (no + / - orientation), with Manchester coding at 1 200 baud over a nominal 22.5 V DC supply, and is allowed to share the same multi-core cable as the 230 V mains feeding the luminaires.1. Architecture · Physikalische Schicht
- Self-contained emergency luminaires (DT1) under DALI-2 support standardised commands for the monthly function tests and annual duration tests required by EN 50172, and these tests can be automated from a central DALI-2 controller.2. Devices · Typ 1 Notbeleuchtung
- DALI-2 supports several application controllers active on the same bus (multi-master), with an arbitration mechanism that prevents conflicts when two controllers try to command the same control gear at the same time.4. Application Controllers · Multi-Master
- A DALI DT1 Function Test simulates a 30-second mains outage to verify that the emergency luminaire switches over to battery; the result (OK / Battery Fault / Lamp Fault) is reported back to the controller for an EN 50172-compliant audit trail.13. Emergency DT1 · Function Test