Question

Self-contained emergency luminaires (DT1) under DALI-2 support standardised commands for the monthly function tests and annual duration tests required by EN 50172, and these tests can be automated from a central DALI-2 controller.

DALI-2LearnDevicesHard
Answer

True

DT1 defines an emergency-specific command set: Function Test (short test, around 30 s, to verify battery-driven turn-on); Duration Test (1 to 3 hours depending on category, to verify autonomy); Inhibit / Re-light for maintenance windows; and Status reporting (battery OK, lamp fault, replacement required). Together they replace the manual walk-round inspection with automated tests and a centralised log, producing substantial savings in buildings with 50+ emergency luminaires.

Preparation tip

Schedule duration tests for low-occupancy windows (Sunday nights) — a failing battery during the test leaves the luminaire dark for several hours afterwards while it recharges.

Waitlist

DALI-2 bank in preparation

The full DALI-2 bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.

Join the waitlist
Want more?

See the 9 other DALI-2 practice questions

Related questions

Question from our independent practice bank. DALI-2 is a registered trademark of DALI Alliance, not affiliated with CertifBus.

Last updated: 19 May 2026

Join the waitlist
DALI-2 waitlist