Smart pumps such as the Grundfos MAGNA3 and the Wilo Stratos MAXO natively support Modbus RTU/TCP, exposing around 50 parameters (power, flow, temperature, status, alarms) and accepting commands (speed, mode), which enables BMS integration without a separate external drive.
True
Several pump ranges embed Modbus directly: Grundfos MAGNA3 / SCALA2 (Modbus integrated), Wilo Stratos MAXO (Modbus and BACnet), KSB MyFlow / Ecoflow (Modbus). Typical exposed measurements are instantaneous power (W), flow (m^3/h), pump head (mCE), fluid temperature, operating hours and start counters, and alarm codes. The control side typically offers mode selection (Auto, Constant Pressure, etc.) and a setpoint. This avoids fitting an external VFD for pumps up to 7.5 kW.
When sizing the BMS integration, remember that these pumps poll slowly internally; a 5-10 s scan interval is plenty and a 1 s cycle just wastes bus time.
Modbus bank in preparation
The full Modbus bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →See the 9 other Modbus practice questions
Related questions
- A Modbus RTU bus on RS-485 supports up to 32 nodes per segment (extendable with repeaters), requires 120 ohm termination resistors at both ends of the bus, and biasing resistors to define the idle state.3. Modbus RTU · RS-485 Multi-Drop
- Which Modbus function code is used to READ the Holding Registers (16-bit read/write registers) of a slave?4. Function codes · Lesen Coils/Register
- Function 0x06 "Write Single Register" writes a single 16-bit Holding Register on a Modbus slave, with both the address and the value encoded on 16 bits each in the request.4. Function codes · Write Single Register (0x06)
- To carry a 32-bit IEEE 754 floating-point value over Modbus (whose registers are 16 bits), two consecutive registers are typically used, with the byte order documented by the slave manufacturer.5. Data encoding · 32-Bit-Float
- Modpoll (focus-sw.com) and mbpoll (Linux/macOS) are free command-line tools used to query a Modbus slave from a PC, indispensable for Modbus diagnostics and integration commissioning.6. Practical · Modpoll / mbpoll