When integrating a new Modbus slave with an unknown byte order, systematically testing the four combinations (ABCD, DCBA, BADC, CDAB) against a known float value is faster than relying on the incomplete or incorrect vendor documentation.
True
Vendor documentation is notoriously ambiguous on byte order: the phrase 'Big Endian' may mean ABCD or BADC depending on the author. The pragmatic field method is to know one value (e.g. a probed temperature of 22.5 degC), read the two registers, decode them with all four byte/word orders, and pick the combination that yields 22.5; once identified, that order is consistent across every float in the same slave. Useful tools include mbpoll with the -F flag, the pymodbus payload utilities, or a quick Python script around struct.unpack.
Mnemonic: ABCD = Big-Endian natural order, CDAB = word swap (most common in Modbus!), BADC = byte swap within each word, DCBA = full reversal (complete Little-Endian). Always carry a known reference value to a commissioning visit; one trusted reading lets you confirm the order in two minutes.
Modbus bank in preparation
The full Modbus bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →See the 9 other Modbus practice questions
Related questions
- Which Modbus variant is today the most widely used for new installations in a modern IT/OT environment?2. Variants · RTU vs. TCP vs. ASCII
- When a Modbus slave cannot execute a request (invalid address, out-of-range value, etc.) it replies with an "Exception Response": the original function code with bit 7 set to 1, followed by an Exception Code explaining the reason.4. Function codes · Exception Responses
- Function 0x05 "Write Single Coil" writes a single binary output on a Modbus slave. The ON value is encoded as 0xFF00 and OFF as 0x0000; any other value is invalid.4. Function codes · Write Single Coil (0x05)
- Function 0x08 "Diagnostic" (serial Modbus RTU/ASCII only) is used to test communications and to read internal error counters of a slave through a set of sub-functions (Return Query Data, Restart Communications, Return Bus Message Count, etc.).4. Function codes · Diagnostic (0x08)
- When a Modbus TCP-to-RTU gateway bridges an RTU segment with several slaves, the Modbus TCP client uses the Unit ID in the MBAP header to target the specific RTU slave behind the gateway.5. Modbus TCP · Unit ID Gateway