Function 0x05 "Write Single Coil" writes a single binary output on a Modbus slave. The ON value is encoded as 0xFF00 and OFF as 0x0000; any other value is invalid.
True
The 0x05 encoding convention is: 0xFF00 means ON (coil = true), 0x0000 means OFF (coil = false), and any other value triggers exception 0x03 "Illegal Data Value". The choice of 0xFF00 rather than 0x0001 is a historical Modbus convention that helps distinguish this command from others. The slave reply is an echo of the request, which serves as confirmation. The dual function code is 0x0F "Write Multiple Coils", which writes several coils in a single frame.
If your driver receives "Illegal Data Value" on a Write Single Coil, the bug is almost always that someone wrote 0x0001 instead of 0xFF00 in the value field.
Modbus bank in preparation
The full Modbus bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →See the 9 other Modbus practice questions
Related questions
- Which Modbus variant is today the most widely used for new installations in a modern IT/OT environment?2. Variants · RTU vs. TCP vs. ASCII
- When a Modbus slave cannot execute a request (invalid address, out-of-range value, etc.) it replies with an "Exception Response": the original function code with bit 7 set to 1, followed by an Exception Code explaining the reason.4. Function codes · Exception Responses
- Function 0x08 "Diagnostic" (serial Modbus RTU/ASCII only) is used to test communications and to read internal error counters of a slave through a set of sub-functions (Return Query Data, Restart Communications, Return Bus Message Count, etc.).4. Function codes · Diagnostic (0x08)
- When a Modbus TCP-to-RTU gateway bridges an RTU segment with several slaves, the Modbus TCP client uses the Unit ID in the MBAP header to target the specific RTU slave behind the gateway.5. Modbus TCP · Unit ID Gateway
- Modern energy meters (Schneider iEM, Socomec Diris, Janitza UMG, Siemens SENTRON) typically expose their measurements (kWh, kVARh, U, I, P, cos phi) over Modbus RTU or TCP, mapped onto standardised or vendor-specific registers.7. KNX integration · Energiezähler