Modern energy meters (Schneider iEM, Socomec Diris, Janitza UMG, Siemens SENTRON) typically expose their measurements (kWh, kVARh, U, I, P, cos phi) over Modbus RTU or TCP, mapped onto standardised or vendor-specific registers.
True
Energy meters are the number-one Modbus use case in modern tertiary BMS. Typical mappings include: Schneider iEM with a documented register list and around 50 measurements; Socomec Diris A40 with about 80 measurements including harmonic THD; Janitza UMG, which is very comprehensive and supports multi-circuit installations; and Siemens SENTRON PAC, integrated with TIA Portal. Good practice is to test the register map with mbpoll before binding it into the BMS, because vendor documentation is sometimes imprecise.
Read at least two energy meters in parallel against a known clamp meter the first time you commission a building: a half-percent discrepancy is normal, a factor of two means a wrong byte order or CT ratio.
Modbus bank in preparation
The full Modbus bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.
Join the waitlist →See the 9 other Modbus practice questions
Related questions
- Which Modbus variant is today the most widely used for new installations in a modern IT/OT environment?2. Variants · RTU vs. TCP vs. ASCII
- When a Modbus slave cannot execute a request (invalid address, out-of-range value, etc.) it replies with an "Exception Response": the original function code with bit 7 set to 1, followed by an Exception Code explaining the reason.4. Function codes · Exception Responses
- Function 0x05 "Write Single Coil" writes a single binary output on a Modbus slave. The ON value is encoded as 0xFF00 and OFF as 0x0000; any other value is invalid.4. Function codes · Write Single Coil (0x05)
- Function 0x08 "Diagnostic" (serial Modbus RTU/ASCII only) is used to test communications and to read internal error counters of a slave through a set of sub-functions (Return Query Data, Restart Communications, Return Bus Message Count, etc.).4. Function codes · Diagnostic (0x08)
- When a Modbus TCP-to-RTU gateway bridges an RTU segment with several slaves, the Modbus TCP client uses the Unit ID in the MBAP header to target the specific RTU slave behind the gateway.5. Modbus TCP · Unit ID Gateway