Question

When an MS/TP segment is not working, the classic checks are: 120 ohm terminations at both ends, bias resistors (typically 680 ohm) installed on one device, a unique MAC per device, the same baud rate on every device, and correct cable polarity.

BACnetLearnPracticalHard
Answer

True

A pragmatic MS/TP troubleshooting checklist runs through six items: (1) 120 ohm terminations present at both physical ends of the segment, (2) bias resistors fitted on a single device (typically the master) so that the idle line is correctly polarised, (3) unique MAC addresses with no duplicates, (4) identical baud rate on every device, (5) correct polarity (e.g. blue/white pairing respected), and (6) a 120 ohm-impedance twisted-pair cable. Around 80 % of MS/TP issues encountered in the field can be traced back to one of these six points.

Preparation tip

Before reaching for a protocol analyser, measure the differential voltage A-B at rest with a multimeter: a value far outside the expected 200-700 mV band almost always points to a termination or bias problem.

Waitlist

BACnet bank in preparation

The full BACnet bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.

Join the waitlist
Want more?

See the 9 other BACnet practice questions

Related questions

Question from our independent practice bank. BACnet is a registered trademark of ASHRAE / BACnet International, not affiliated with CertifBus.

Last updated: 19 May 2026

Join the waitlist
BACnet waitlist