Distances and limits of the KNX TP1 bus

All critical lengths on a single sheet

3 minFree accesstopologiecabledistancesegment

Memorisable in 3 minutes. Keep at hand during the Basic exam (open book) and to check your wiring diagrams at the design stage.

⚡ The 4 figures to know by heart

LimitValueMnemonic
Max distance device ↔ power supply (PSU)350 m"350 = one kilometre across 3 return paths"
Min distance between 2 PSUs on the same line200 m"200 minimum so they don't interfere"
Max distance between any 2 devices700 m"700 = 2 × 350, one device either side of the PSU"
Max cumulative length of a segment1 000 m"1 km per segment, period"

🧮 Structural limits

ElementMaximumNotes
Devices per segment (without repeater)64Native TP1 limit
Segments per line (with repeaters)4I.e. 4 × 64 = 256 devices/line max
Lines per area15Linked via Line Couplers
Areas per installation15Linked to the backbone via Area Couplers
Backbone1Area "0" (reserved)
Total max devices without repeaters14 40015 × 15 × 64
Total max devices with repeaters57 60015 × 15 × 256

🔌 Standard bus cable

CharacteristicValue
TypeJ-Y(St)Y 2 × 2 × 0.8 mm²
Conventional colourGreen (but not mandatory by standard)
PolarisationYes (red = +, black = −)
Voltage30 V DC SELV
Isolation from 230 V4 kV (separator or insulated sheath required)
Coexistence with SELV cablesAllowed (telephone, alarm, other buses)
Bus terminationNone required (≠ RS-485)
Permitted topologyLine, star, tree — closed loop forbidden
Min bending radius~8 × outer diameter

⚠️ Classic pitfalls in exams / on site

Pitfall 1 — Confusing 350 / 700 m

  • 350 m = device ↔ PSU (the most quoted)
  • 700 m = between any two devices (often confused with the previous one, classic T/F exam item)

Pitfall 2 — "Segment" vs "Line"

  • Segment = physical portion with max 1 PSU + ≤ 64 devices
  • Line = logical entity (ID in the ETS topology), can contain 1 to 4 segments
  • The individual address Z.L.D identifies the line, not the segment

Pitfall 3 — Dedicated PSU

  • A bus PSU must be dedicated (with choke to decouple signal/power)
  • NEVER use a bus PSU to power an external 24 V actuator
  • NEVER use a generic 30 V PSU without a choke (telegrams won't pass)

Pitfall 4 — Polarity

  • The bus IS polarised: swapping red/black prevents communication
  • Some modern devices have protection but it is not standard

💡 Key takeaway

350 / 200 / 700 / 1000 — four figures, memorise them in order "device ↔ PSU, two PSUs min, two devices max, one segment". Everything else follows.

Sources:

  • KNX Specifications V3.0.0 (public)
  • Hager BAC071, Porto KNX Basic Course
Practice now

Put your KNX Basic knowledge into practice

10 explained practice questions, no sign-up. Find your first topics to revisit.

KNX Basic cheatsheets
← All cheatsheets
KNX BASIC

Your next study session starts with 10 questions.

Try the questions and explanations without an account. Then choose an access period that fits your preparation.

+1/−0,5/0 official scoringFR·EN·DE interface and explanations9 from · one-time payment
Newsletter

Keep your KNX preparation moving

We'll email you when new KNX questions, a guide or a tool is published. No spam.

Unsubscribe in 1 click. No sharing with third parties.