Cheatsheet

Distances and limits of the KNX TP1 bus

All critical lengths on a single sheet

3 minFree accesstopologiecabledistancesegment
Maximum distances on a KNX TP segment: 350 m between the power supply and a device, 700 m between two devices, 1 000 m of cable in total.
The three lengths to remember for a KNX TP bus segment. CertifBus diagram.

Memorisable in 3 minutes. Keep at hand during the Basic exam (open book) and to check your wiring diagrams at the design stage.

⚡ The 4 figures to know by heart

LimitValueMnemonic
Max distance device ↔ power supply (PSU)350 m"350 = one kilometre across 3 return paths"
Max centralised PSUs on the same line2"2 at most, minimum spacing per the manufacturer's data"
Max distance between any 2 devices700 m"700 = 2 × 350, one device either side of the PSU"
Max cumulative length of a segment1 000 m"1 km per segment, period"

🧮 Structural limits

ElementMaximumNotes
Devices per line segment64 (TP-64) · 256 (TP-256, since 2019)Depends on the power supply and the products
Segments per line4Joined by at most 3 line repeaters
Lines per area15Linked via Line Couplers
Areas per installation15Linked to the backbone via Area Couplers
Backbone1Area "0" (reserved)
Full TP networkmore than 61,00015 areas × 16 lines (main line included) × 255 devices

🔌 Standard bus cable

CharacteristicValue
TypeJ-Y(St)Y 2 × 2 × 0.8 mm (conductor Ø, ≈ 0.5 mm² cross-section)
Conventional colourGreen (but not mandatory by standard)
PolarisationYes (red = +, black = −)
Voltage30 V DC SELV
Test voltage (course example cables)4 kV YCYM · 2.5 kV J-Y(St)Y; keep apart from 230 V (separator or insulated sheath)
Coexistence with SELV cablesAllowed (telephone, alarm, other buses)
Bus terminationNone required (≠ RS-485)
Permitted topologyLine, star, tree — closed loop forbidden
Min bending radius~8 × outer diameter

⚠️ Classic pitfalls in exams / on site

Pitfall 1 — Confusing 350 / 700 m

  • 350 m = device ↔ PSU (the most quoted)
  • 700 m = between any two devices (often confused with the previous one, classic T/F exam item)

Pitfall 2 — "Segment" vs "Line"

  • Segment = physical portion with its own power supply + ≤ 64 devices (TP-64) or ≤ 256 (TP-256)
  • Line = logical entity (ID in the ETS topology), can contain 1 to 4 segments
  • The individual address Z.L.D identifies the line, not the segment

Pitfall 3 — Dedicated PSU

  • A bus PSU must be dedicated (with choke to decouple signal/power)
  • NEVER use a bus PSU to power an external 24 V actuator
  • NEVER use a generic 30 V PSU without a choke (telegrams won't pass)

Pitfall 4 — Polarity

  • The bus IS polarised: swapping red/black prevents communication
  • Some modern devices have protection but it is not standard

💡 Key takeaway

350 / 2 / 700 / 1000 — four figures, memorise them in order "device ↔ PSU, two PSUs max per line, two devices max, one segment". Everything else follows.

Sources:

  • KNX Specifications V3.0.0 (public)
  • Hager BAC071, Porto KNX Basic Course
KNX TP topology: the backbone line joins backbone couplers 1.0.0 and 2.0.0; main line 1.0 joins line couplers 1.1.0 and 1.2.0; each line carries its devices 1.1.1, 1.1.2, 1.1.3.
Areas, lines and devices of a KNX TP installation, with the coupler addresses. CertifBus diagram.

Practice now

Put your KNX Basic knowledge into practice

10 explained practice questions, no sign-up. Find your first topics to revisit.