Window contacts in a room can switch the HVAC system to frost protection mode through a KNX logic link.
True
When a window contact reports 'open', it is standard practice to drive the room controller's HVAC mode object (DPT 20.102) to Frost/Heat protection, or to force its setpoint down to the frost protection value. The link is usually implemented either directly by parametrising the room controller or through a simple logic block that translates the 1-bit window state into the matching mode telegram. This avoids heating against an open window and protects pipes during winter ventilation.
Always add a short delay (typically 1-2 minutes) before reverting to Comfort/Standby to avoid mode flapping when the window is briefly tilted.
Keep going with the full KNX Advanced bank
Keep going with the full KNX Advanced bank: unlimited timed mock exams, detailed answers, history. From €9 (one-time payment).
See pricing — from €9 →See the 9 other KNX Advanced practice questions
Related questions
- On highly sensitive KNX Secure installations (strategic sites, defence buildings), the keyring keys can be stored in a Hardware Security Module (HSM) attached to ETS, guaranteeing that the keys never leave the secure hardware even during download operations.X. KNX Secure · HSM (Hardware Security Module)
- In KNXnet/IP Routing, several IP Routers on the same VLAN share traffic via multicast 224.0.23.12, forming an IP backbone with no master-slave hierarchy between the routers.1. Couplers · IP Routing vs. Tunneling
- A Group Object configured with the flags C+R+T+U but without W cannot receive writes from other devices - it can only be modified locally by its own device.2. Flags · Flag-Kombinationen
- DPT 20.102 (HVAC Mode) encodes the four standard modes - Comfort (1), Standby (2), Economy (3) and Building Protection (4) - and is applied as a cascade from the currently active mode.4. HVAC Control · HVAC-Modi
- A KNX/DALI gateway allows up to 64 DALI ballasts on a single DALI bus to be driven from KNX commands, with addressing either individual or by DALI group.5. Lighting Control · DALI-Gateway