Question

The BACnet Notification Class object defines who must receive alarm notifications (Recipient_List), with what priority, and whether acknowledgement is required.

BACnetMock examObject typesHard
Answer

True

A Notification Class is the central configuration for alarm routing. The key properties are Recipient_List (the list of destinations, defined either by Device + Process_ID or by a direct address, filterable by day of week and time of day), Priority (a 0-255 ordering value) and Ack_Required (which event transitions among TO_OFFNORMAL, TO_FAULT and TO_NORMAL must be acknowledged by a user). Risk-bearing objects (an AI for a temperature probe, a BV for an intrusion alarm) reference a Notification Class through their Notification_Class property. This allows centralised, configurable alarm-flow management.

Preparation tip

Always create at least three Notification Classes (critical, standard, info) on day one: refactoring the alarm routing later when 500 points already reference Notification Class 1 is a painful migration.

Waitlist

BACnet bank in preparation

The full BACnet bank isn't available yet. Drop your email to get notified at launch and grab an early-bird discount.

Join the waitlist
Want more?

See the 9 other BACnet practice questions

Related questions

Question from our independent practice bank. BACnet is a registered trademark of ASHRAE / BACnet International, not affiliated with CertifBus.

Last updated: 19 May 2026

Join the waitlist
BACnet waitlist
KNX BASIC & ADVANCED

Ready to find out where you really stand?

10 free questions every day, no account needed. Full access only if you decide to go all the way.

+1/−0,5 official scoringFR·EN·DE interface and explanations9 from · one-time payment
Newsletter

Get launch announcements

We'll email you when a new bank ships (BACnet, Modbus, etc.) or a new tool. Plus an early-bird discount on first purchases. No spam.

Unsubscribe in 1 click. No sharing with third parties.