A KNX "Functional Block" defines a standardised set of Group Objects for a given function (e.g. simple lighting actuator, thermostatic valve), guaranteeing interoperability between manufacturers for that function.
True
Functional Blocks are standardised interworking templates. Examples include FB Light Switch (DPT 1.001 command + DPT 1.001 status), FB Dimming (DPT 1.001 + 3.007 + 5.001) and FB HVAC Room Controller (10+ standardised Group Objects). Interworking certification verifies that products implement these FBs correctly, which is what guarantees that one manufacturer can be substituted for another without reprogramming.
When specifying a product, demand the Functional Block compliance list, not just the "KNX certified" logo — the logo alone does not guarantee a clean substitution.
Keep going with the full KNX Advanced bank
Keep going with the full KNX Advanced bank: unlimited timed mock exams, detailed answers, history. From €9 (one-time payment).
See pricing — from €9 →See the 9 other KNX Advanced practice questions
Related questions
- On highly sensitive KNX Secure installations (strategic sites, defence buildings), the keyring keys can be stored in a Hardware Security Module (HSM) attached to ETS, guaranteeing that the keys never leave the secure hardware even during download operations.X. KNX Secure · HSM (Hardware Security Module)
- In KNXnet/IP Routing, several IP Routers on the same VLAN share traffic via multicast 224.0.23.12, forming an IP backbone with no master-slave hierarchy between the routers.1. Couplers · IP Routing vs. Tunneling
- A Group Object configured with the flags C+R+T+U but without W cannot receive writes from other devices - it can only be modified locally by its own device.2. Flags · Flag-Kombinationen
- DPT 20.102 (HVAC Mode) encodes the four standard modes - Comfort (1), Standby (2), Economy (3) and Building Protection (4) - and is applied as a cascade from the currently active mode.4. HVAC Control · HVAC-Modi
- A KNX/DALI gateway allows up to 64 DALI ballasts on a single DALI bus to be driven from KNX commands, with addressing either individual or by DALI group.5. Lighting Control · DALI-Gateway