Tunable White control (variable colour temperature, e.g. 2700 K warm to 6500 K cool) over KNX typically uses two distinct DPTs: one for the overall intensity (DPT 5.001, %) and one for the colour temperature (DPT 7.600, K).
True
DPT 7.600 is Absolute Colour Temperature in Kelvin (16 bits, technical range 0-65535 but usable range 2000-10000 K). Combined with DPT 5.001 for intensity, it allows independent control of the two dimensions. This is the standard binding for Tunable White luminaires using a warm-white plus cool-white dual-channel LED.
Lock the controllable colour-temperature range to the values supported by the luminaire datasheet: a command for 10000 K to a luminaire capped at 6500 K silently clamps and confuses end users about the actual behaviour.
Keep going with the full KNX Advanced bank
Keep going with the full KNX Advanced bank: unlimited timed mock exams, detailed answers, history. From €19 (one-time payment).
See pricing — from €19 →See the 9 other KNX Advanced practice questions
Related questions
- On highly sensitive KNX Secure installations (strategic sites, defence buildings), the keyring keys can be stored in a Hardware Security Module (HSM) attached to ETS, guaranteeing that the keys never leave the secure hardware even during download operations.X. KNX Secure · HSM (Hardware Security Module)
- What is the principle of Constant Light Control regulation in KNX?5. Lighting Control · Constant Light Control
- A KNX presence detector configured with a 15-minute timeout keeps the lighting on for that duration after the last detection, then automatically switches it off.5. Lighting Control · Präsenzerkennung
- The emergency lighting of a building CANNOT be driven by KNX alone: it must comply with dedicated standards (NF EN 1838, EN 50172) that require a self-contained system with a backup battery.5. Lighting Control · Sicherheitsbeleuchtung
- A standard KNX end-of-works deliverable typically includes the .knxproj project file, printed documentation (topology, Group Address table, electrical schematics), functional-test reports, user training, and a separate .knxkeys keyring file when KNX Secure is used.13. Project best practices · Projektdokumentation