Glossary term
Flag T
flagBasics
Also known as
Transmit
Definition
Flag allowing the GO to send a Group Value Write on the bus when its value changes locally.
Questions using this term
- A standard KNX end-of-works deliverable typically includes the .knxproj project file, printed documentation (topology, Group Address table, electrical schematics), functional-test reports, user training, and a separate .knxkeys keyring file when KNX Secure is used.13. Project best practices · Projektdokumentation
- A Modbus RTU bus on RS-485 supports up to 32 nodes per segment (extendable with repeaters), requires 120 ohm termination resistors at both ends of the bus, and biasing resistors to define the idle state.3. Modbus RTU · RS-485 Multi-Drop
- A compact PROFIBUS DP slave has an I/O configuration that is frozen at manufacturing time (e.g. a 32-bit encoder, a 4-module pressure transmitter), which simplifies configuration but limits flexibility.4. GSD files · Kompaktslave
- PROFIBUS PA transmitters typically implement a standardised "PA Profile Device": Differential Pressure (DP transmitter), Pressure (P), Temperature (T), Level (L) and Analytical (pH, conductivity), with harmonised function blocks and parameters.9. Profiles · PA-Profile-Devices
- A typical chemical plant uses PROFIBUS DP as backbone (DCS level 2) plus PROFIBUS PA segments for the transmitters located in Ex ia / ib zones (lower process layers), an architecture which will remain dominant against PROFINET-APL for another 5-10 years in process industry.21. Use cases · Anwendungsfall Chemieanlage